Thanks for your submission. A customer service agent will be in touch soon to help you further.
Features & Benefits
- Custom engineered design, depending on the unique application type
- Safe and efficient in operation: fully grounded system with zero electrical potential on pipe surfaces, can be used in Class 1 Division 2 and Zone 2 hazardous areas
- Long circuit lengths (up to 15 miles/25 km), minimize operating and installation costs by reducing the required number of power supply points
- Advanced control systems with multiple temperature inputs to adequately monitor and control longline heat tracing
- Reliable during long life: entire circuit is encapsulated within rugged heat tubes and steel boxes
Specifications
Specifications
- Supply Voltage
- 0 – 2500 V
- Max Power Output
- 150 W/m
- Max Power Output
- 45.7 W/ft
- Max Maintain or Continuous Exposure Temperature, Power On
- 250 °C
- Max Maintain or Continuous Exposure Temperature, Power On
- 482 °F
- Outer Jacket Material
- Fluoropolymer
- Ground Path Type
- None
- Area Classification
- Non-Hazardous; Hazardous
- Min Installation Temperature
- -40 °C
- Min Installation Temperature
- -40 °F
Catalog Number
|
Item Name
|
Nominal Cable Weight
|
Nominal Cable Weight
|
Min Bending Radius @ -40°C
|
Min Bending Radius @ -40°F
|
Outer Diameter
|
Outer Diameter
|
AWG Size
|
---|---|---|---|---|---|---|---|---|
P000001475 | STS-HT/13.25-WIRE | 233 g/m | 0.16 lb/ft | 60 mm | 2.4 in | 9.9 mm | 0.39 in | 6 |
P000000635 | STS-HT/21.25-WIRE | 333 g/m | 0.22 lb/ft | 77 mm | 3 in | 11.2 mm | 0.44 in | 4 |
P000001474 | STS-HT/33.25-WIRE | 500 g/m | 0.33 lb/ft | 84 mm | 3.3 in | 13.2 mm | 0.52 in | 2 |